Online U.P.S. With Isolation Transformer

Available Configuration

Single Phase Input Single Phase output – 1KVA to 15 KVA

 

SUPER SERIES MODELS

Single Phase Input Three Phase output – 5KVA to 15 KVA

Three Phase Input Single Phase output – 5KVA to 40 KVA

Three Phase Input Three Phase output – 5KVA to 150 KVA

Add to Wishlist
Add to Wishlist
Categories: ,

TECHNICAL SPECIFICATIONS

RATED POWER 1KVA to 15KVA5KVA to 40 KVA5KVA to 15KVA5KVA to 150KVA
PHASE1 Phase3 Phase 1  Phase1 Phase 3 Phase3 Phase 3 Phase
INPUT VOLTAGE170V-270V

340V-460V, 3 Phase

4 WIRE / 5 WIRE

340V-460V

340V-460V, 3-Phase

4 WIRE / 5 WIRE

FREQUENCY45-55Hz45-55Hz45-55Hz45-55Hz
DC VOLTAGE120V-192V240V-360V180V-192V240V-360V
TECHNOLOGYMicrocontroller based High Frequency PWM using IGBT as Principal Switching Device / DSP based design

INVERTER

OUTPUTVOLTAGE :  230V ± 1%       200/380/400/415 AC+ 1% 3PHASE, 4 WIRE / 5 WIRE

OUTPUT FREQUENCY:  Crystal Controlled     50 Hz ± 0.01% or 60Hz ± as required

OUTPUT WAVE FORM:  Pure Sinewave

OUTPUTISOLATION:  Galvanic Isolation Transformer provided as standard design feature

HARMONIC:  Less than 3% for Linear Load and less than 5% for Non- Linear Load

DISTORTION | THD |

POWER FACTOR:  08% to Unity

PEAK SURGE:   300% for 3000 ms

HANDLING CAPACITY

EFFICIENCY:   Better than 92%

OVERLOAD CAPACITY:   125% for 5 minutes, 150% for 60 seconds

CREST FACTOR:    4:1

TRANSIENT RECOVERY:    within 3 cycle

BYPASS:    Manual Bypass / Static Bypass, transfer  time < 2ms

BATTERY CHARGER

CHARGER TYPE:   Constant Voltage Constant Current. Trickle / Float and Boost /IGBT Charger | optional |

CHARGING TIME:    8 to 10 hours

CHARGING CURRENT :    @10% of the Rated Battery AH

OPERATING CONDITIONS

OPERATING TEMP. :    0°C to 50°C

RELATIVE HUMIDITY:    90% Non-Condensing

NOISE LEVEL :    less than 55db at 1 meter

COOLING:   forced Air Cooling by Fan

ENCLOSURE TYPE:   IP 21 or IP 31

TRANSFER TIME:   0 millisecond

INDICATIONS

LCD DISPLAY:    Input Voltage, Output Voltage, Input Frequency, Output Frequency, Output Current, Low Battery, Battery Current, Battery Voltage

AUDIBLE ALARM:    Battery Low, Mains Low, Fault AC Over, Overload

PROTECTION:   Output | Input Cut-Off, Overload, Short Circuit protection through Fuses and sensing as required Battery Over Voltage|Under Voltage Cut-Off • Reverse Polarity of Battery

COMMUNICATION & MANAGEMENT:       Ethernet optional |

GALVANIC ISOLATION: Superior full time isolation in built into all DATAVISION UPS. Output is fully isolation try double conversion and isolation transformer, No need to have extra isolation as required for imported system.

COMPONENTS MAKE: All components used in DATAVISION UPS are of high quality and reputed make:

  • Capacitors: Alcon/Rescon
  • IGBT : Mitsubishi, Semikron, Toshiba
  • Rectifiers: Semicron,IXYX
  • Electrolytic Capacitor: Keltrons, Philips, CDIL.

 

ALSO AVAILABLE

  1. Hot Standby Model
  2.  IGBT Charger for Better Efficiency Custom Built Online UPS like 60Hz Frequency & 110V Output 3 Phase |

 

IGBT ONLINE UPS SYSTEMS

SALIENT FEATURES

> Wide Input Window

> Latest Microprocessor based technology | DSP technology

> Unlimited Back up

> In built Galvanic Isolation Transformer for better performance  

> Sixth Generation Low Exhaust IGBT

> 100% unbalanced Load acceptable

> User friendly Screen Display

> Ability to work with al critical loads and compatible

> Cold Start Function

> Onsite up-gradation of UPS by 25% of its present capacity

> Peak Surge Handling Capacity of 300% for 3000ms

> RS232 Communication Port optional |

IGBT ONLINE UPS SYSTEM

Salient Features:

  • Wide Input Window.
  • Latest Microprocessor based technology / DSP technology > Unlimited Back up.
  • In-built Galvanic Isolation Transformer for better performance > Advance Battery Management.
  • Sixth Generation Low Exhaust IGBT > 100% unbalanced Load acceptable > Static and Manual bypass.
  • User friendly Screen Display > Ability to work with all critical loads and compatible with most type of Generators.
  • Cold Start Function On-site up-gradation of UPS by 25% of its present capacity.
  • Peak Surge Handling Capacity of 300% for 3000ms.
  • RS232 Communication Port [optional].

CVCF (CONSTANT VOLTAGE CONSTANT FREQUENCY)

  • 5KVA to 50KVA.
  • Ultimate solution for.
  • Colour Sortex Machines and Packaging Machines.
  • Provides Constant Voltage.
  • Provides Constant Frequency.
  • Ensures isolated Voltage.
  • Protects the load and itself from Supply Adversities.

 

Technical Specifications of IGBT
ONLINE UPS SYSTEMS

Avaialable Configuration
Single Phase Input Single Phase Output – 5 KVA to 15 KVA
SUPER SERIES MODELS
Single Phase Input Three Phase Output – 5 KVA to 15 KVA
Three Phase Input Single Phase Output – 5 KVA to 40 KVA
Three Phase Input Three Phase Output – 5 KVA to 150 KVA
TECHNICAL SPECIFICATIONS
RATEDPOWER1 KVA to 15 KVA5KV to 40KVA5KVA to 15KVA5KVA to 150KVA
PHASE1-Phase3Phase-1Phase1 Phase-3Phase3Phase -3 Phase
INPUT    
INPUT VOLTAGE170v-270v290V-460V, 3PHASE170V-270V290V-460V, 3-PHASE
  4 WIRE | 5 WIRE 4 WIRE | 5 WIRE
FREQUENCY45-55Hz45-55Hz45-55Hz45-55Hz
DC VOLTAGE120V-192V240V-360V180V-192V240V-360V
TECHNOLOGYMicrocontroller based High Frequency PWM using IGBT as Principal Switching Device/ DSP based design.
INVERTER
OUTPUT VOLTAGE230V±1%200/380/400/415 AC + 1% 3-PHASE, 4 WIRE | 5 WIRE
OUTPUT FREQUENCYCrystal Controlled 50 Hz +0.01% or 60 Hz + as required
OUTPUT WAVE FORMPure Sinewave
OUTPUT ISOLATIONGalvanic Isolation Transformer provided as standard design feature
HARMONIC DISTORTION
(THD)
Less than 3% for Linear Load and less than 5% for Non-Linear Load
POWER FACTOR0.8% to Unity
PEAK SURGE HANDLING CAPACITY300% for 3000 ms
EFFICIENCYBetter than 82%
OVERLOAD CAPACITY125% for 5 minutes, 150% for 60 seconds
CREST FACTOR4:1
TRANSIENT RECOVERYwithin 3 cycle B
BY PASSManual Bypass / Static Bypass, transfer time < 2ms
BATTERY CHARGER
CHARGER TYPEConstant Voltage Constant Current, Trickle | Float and Boost | IGBT Charger | optional
CHARGING TIME8 to 10 hours
CHARGING CURRENT@ 10% of the Rated Battery AH
OPERATING CONDITIONS
OPERATING TEMP0°C to 50°C
RELATIVE HUMIDITY90% Non-Condensing
NOISE LEVELless than 55db at 1 meter
COOLINGforced Air Cooling by Fan
ENCLOSURE TYPEP21 orIP31
TRANSFER TIME0 millisecond
INDICATIONS
LCD DISPLAYInput Voltage, Output Voltage, Input Frequency, Output Frequency, Output Current, Low Battery, Battery Current, Battery Voltage
AUDIBLE ALARMBattery Low, Mains Low, Fault, AC Over, Overload
PROTECTIONOutput | Input Cut-Off, Overload, Short Circuit protection through Fuses and sensing as required Battery Over Voltage | Under Voitage Cut-Off » Reverse Polarity of Battery
COMMUNICATION & MANAGEMENTEthernet (optional)
GALVANIC ISOLATIONSuperior full time isolation is built into all.Outputs fully isolated by double conversion and isolation transformer. No need to have extra isolation as required for imported systems.
COMPONENTS MAKEAll components used in are of high quality and reputed make.
 Capacitors : Alcon | Rescon
 IGBT : Mitsubushi, Semikron, Toshiba
 Rectifiers : Semicron, IXYX
 Electrolytic Capacitor : Keltrons, Philips, CDIL

Reviews

There are no reviews yet.

Be the first to review “Online U.P.S. With Isolation Transformer”

Your email address will not be published. Required fields are marked *