Technical Specifications of MF Series 1-3KVA
|
| INPUT |
| Nominal Voltage |
220V/230V/240V AC (1Ph+N+PE, 3 Wire) |
| Operating Voltage Range |
90V~300V AC Load Dependent |
| Operating Frequency Range |
50/ 60 Hz ± 10% (Auto Sensing) |
| Output |
| Output Voltage/Power
Factor |
220V/230V/240V AC/±1%/ 0.8 Std., 0.9 Optional |
| Output Frequency |
Auto Sensing 50 / 60 Hz± 1~10% Sync Mode (Configurable), 50/60 Hz ± 0.1 Hz Battery Mode |
| Harmonic Distortion (THDv) |
<2% (Linear load), <5% (Non Linear Load) |
| Crest Factor |
0.125694444 |
| Efficiency |
Up to 94% Dual Conversion Mode, 99% ECO Mode |
| Battery |
| DC Voltage |
36V |
96V |
| Battery Type & Number |
|
12V/7AH x 03 |
|
12V/7AH x 08 |
| Backup Time (50% Load) |
|
12 Min |
|
19 Min |
| Backup Time (Full Load) |
|
05 Min |
|
08 Min |
| Charge Current |
6A |
1A |
6A |
1A |
| Typical Recharge Time |
8 Hours (90% of full capacity) |
| System Features |
| LCD Indication |
Input Voltage/Frequency, Output Voltage/Frequency, Battery Voltage, Load Watt/VA and %, Inverter Temperature, Operation Mode such as ‘On line’, ‘ON batt’ or ‘On Bypass’, Fault Codes, Battery & Load Bar graph |
| LED Indication |
Normal Operation, Bypass, Abnormal, Fault and Battery Mode |
| Alarms / Protection |
Batt. Low, DC High, Inverter Under/Over Voltage, UPS Over Load, Short Circuit, Fan Failure and UPS Fault. |
| Overload Capability |
≤ 125% for 10 min,>125~150% for 1 min,>150% for 200 ms |
| Transfer Time/Surge |
AC to Battery: 0ms, Inverter to Bypass: 4ms (Typical); Filter with surge |
| Suppression |
suppression Protection TVSS. |
| Environmental |
| Temperature |
Operating: 0~45℃, Storage: -10℃ ~ 55C |
| Humidity / Altitude |
0~95% RH non-condensing/<1500 M |
| Noise |
Low Audible Noise Level |
| Physical |
| Dimension WxDxH (mm) |
144x400x215
192x469x399 |
| Net Weight (kg) |
11.350 Kg
26.570 Kg |
| Standards |
| Quality |
ISO 9000, ISO 14001, OHSAS 18001, ISO 27001, BIS, RoHS |
| Safety |
IEC/EN62040-1 |
| EMC / Performance
Communication Interface |
IEC/EN62040-2; IEC/EN62040-3, Complying to CE |
| Standard |
RS-232 |
| Optional |
SNMP / ModBus / Dry Contact / USB / RS-485 |
| Monitoring Software |
NetAgent Utility v5.8 / View Power / UPSilon 2000 / Muser 4000 |
Reviews